风机盘管(四管制)性能参数表
参数/型号 |
FP-34 |
FP-51 |
FP-68 |
FP-85 |
FP-102 |
FP-136 |
FP-170 |
FP-204 |
FP-238 |
|
额定风量m³/h |
** |
350 |
540 |
700 |
850 |
1020 |
1360 |
1740 |
2050 |
2400 |
中档 |
250 |
340 |
480 |
580 |
690 |
1000 |
1250 |
1560 |
2100 |
|
低档 |
160 |
240 |
320 |
390 |
460 |
650 |
800 |
1080 |
1620 |
|
三排管额定冷量W |
** |
2080 |
3250 |
4180 |
4610 |
5520 |
7650 |
9300 |
10800 |
12850 |
中档 |
1780 |
2880 |
3450 |
4230 |
4490 |
6850 |
8120 |
9200 |
11050 |
|
低档 |
1660 |
2450 |
2870 |
3760 |
3930 |
6110 |
7350 |
8400 |
8650 |
|
单排管额定热量W |
1451 |
176 |
2901 |
3626 |
4351 |
5775 |
6887 |
7933 |
8898 |
|
输入功率W |
WA(M)LA |
35 |
45 |
55 |
75 |
78 |
110 |
132 |
170 |
200 |
WAG30 |
42 |
55 |
65 |
82 |
102 |
146 |
168 |
190 |
250 |
|
WAG50 |
47 |
62 |
75 |
95 |
110 |
165 |
190 |
230 |
280 |
|
KM2 |
37 |
52 |
62 |
76 |
96 |
134 |
152 |
189 |
228 |
|
噪声值dB |
WA(M)LA |
36 |
39 |
40 |
41 |
42 |
44 |
46 |
47 |
50 |
WAG30 |
39 |
42 |
43 |
44 |
45 |
47 |
48 |
50 |
53 |
|
WAG50 |
41 |
44 |
45 |
46 |
47 |
49 |
50 |
52 |
54 |
|
KM2 |
37 |
39 |
40 |
41 |
43 |
44 |
45 |
47 |
50 |
|
三排冷水盘管 |
水量kg/h |
357 |
522 |
692 |
825 |
985 |
1366 |
1660 |
1929 |
2295 |
水阻kPa |
3.1 |
8.2 |
13.4 |
25.6 |
28.4 |
14.4 |
21.8 |
32.5 |
49.5 |
|
一排冷水盘管 |
水量kg/h |
127 |
190 |
252 |
315 |
377 |
503 |
628 |
52 |
878 |
水阻kPa |
5.2 |
10.7 |
16.8 |
29.9 |
36.1 |
19.5 |
26.7 |
35 |
45 |
|
机组重量kg |
WA WAG |
16 |
18 |
21 |
24 |
27 |
36 |
41 |
47 |
52 |
LA |
24 |
26 |
30 |
32 |
37 |
45 |
48 |
52 |
56 |
|
WM |
26 |
31 |
33 |
41 |
46 |
59 |
62 |
66 |
68 |
|
KM2 |
19 |
23 |
28 |
29 |
33 |
41 |
44 |
46 |
51 |
注:1.表中冷量、热量测定条件(JB/ T4283-91)为:
2.供冷:DB27℃/WB19.5℃,TW1=7℃,TW2=12℃
3.供热:DB21℃,TW1=60℃
4.高静压机组额定风量是机外30/50Pa时的测定值,其余机组额定风量,不带风口和过滤器是机外余压12Pa时的测定值,带风口和过滤器是机外余压为零时的测定值;
5.如使用工况与标准工况不同,请用样本后附修正系数进行修正,方法为;实际制冷(热)量=额定制冷(热)量*工况修正系数;
6.表中的噪声值是在消声室内,离机组各表面1米处(GB9068)测定的声压级噪声值。